~ 25 ~
The zone expander board can accommodate up to (4) initiating device
zones. Two zone cards per expander board with (2) initiating device zones
per card. Zones can be implemented as Class A/B detection, waterflow or
switch supervisory circuits depending on the jumper configuration of the
ZC-91A card. The Expander Board can also accommodate (2) Alarm B
Notification Control cards (AE-91) with (1) Notification Appliance
circuit per card.
H@1>45B
?1B4
#
9C@<1I&1>5<
,1B91D9?>C
*For zone field wiring see Expander Board field wiring page of this manual. For AE-91 field wiring see Option “U”
page of this manual. For dual temperature zone card field wiring see ZC-95 field wiring page of this manual.
**For solenoid circuit field wiring see RS-1 field wiring page of this manual.
Also reference the Installation Wiring Diagram (IWD).
Standard expander board: Used to increase system capabilities.
Accommodates up to (2) cards
#
Metered expander board: Used to increase system capabilities and
compatible with alarm point location meter. Accommodates up to (2)
cards
0 Standard system zone card: Contains (2) Detection Circuits per card.
0# Metered system zone card: Contains (2) Detection Circuits per card (Metered zone card requires EB-91AM)
0- Waterflow zone card: Contains (2) Detection Circuits per card.
0 Intrinsic zone card: Contains (2) Intrinsic Detection Circuits per card.
) Switch Supervisory zone card: Contains (2) Detection Circuits per card.
)$" Non-Latching switch supervisory zone card: Contains (2) Detection Circuits per card.
Alarm Notification Appliance circuit card: Contains (1) Alarm Notification Appliance circuit per card.
() Solenoid release circuit card: Contains (1) Solenoid Release Circuit & (1) Detection Circuit per card.
&&""%(#&&(%, )/)*#)%$"/