Protectowire 2000 FireSystem Specifiche Pagina 17

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 63
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 16
))5B95C9B55D53D9?>
&B513D9?>5<E75?>DB?<&1>5<%@5B1D9?>
>CD1<<1D9?>*5CD1>4#19>D5>1>35
%@5B1D9?>1<%ED<9>5
 $?B=1<)D1>42I?>49D9?>
a) “AC ON” Indicator (Green) illuminated.
 &?G5B)E@5BF9C9?>
@?G5BC?EB35619<EB5
a) “AC ON” Indicator (Green) OFF.
b) System trouble buzzer ON (Pulsing) - Press “SUP./TRO. SIL.” button to silence.
c) “SYS. TRO.” Indicator (Yellow) Flashing.
d) Restore AC power to resume standby condition.
@?G5BC?EB35619<EB5
a) “SYSTEM. TROUBLE / SUP.” Indicator (Yellow) Flashing.
b) “BATTERY OUT” Indicator (Yellow) ON.
c) System trouble buzzer ON (Pulsing) - Press “SUP. / TRO. SIL.” button to silence.
d) Restore DC power to resume standby condition.
 <1B=5D53D9?>9B3E9DC
)8?BD9>45D53D9?><??@45F935?B61E<D<1B=?>49D9?>
a) “SYSTEM ALARM” Indicator (RED) ON.
b) “ZONE ALARM” Indicator (RED) ON.
c) All alarm notification appliance circuits activated. Press “AL. SIL.” button to silence, “AL. SIL.” Indicator (Yellow) Flashing.
d) Restore detection circuit or initiating device. Press “SYS. RST.” button to return to standby condition.
%@5>9>45D53D9?><??@0?>5*B?E2<5)ICD5=*B?E2<5
a) “SYSTEM TROUBLE / SUP.” Indicator (Yellow) Flashing.
b) “ZONE TROUBLE” Indicator (Yellow) ON.
c) System trouble buzzer ON (Pulsing) - Press “SUP./TRO. SIL.” button to silence.
d) Clear detection circuit to return to standby condition.
 $?D96931D9?>@@<91>359B3E9DC
)8?BD9>>?D96931D9?>1@@<91>3539B3E9D<??@<)8?BD
a) “SYSTEM TROUBLE / SUP” Indicator (Yellow) Flashing.
b) “ALARM SHORT” Indicator (Yellow) ON.
c) System trouble buzzer ON (Pulsing) - Press “SUP. / TRO. SIL.” button to silence.
d) Clear (repair) short to circuit to return to standby condition.
%@5>9>>?D96931D9?>@@<91>3539B3E9D<??@<%@5>
a) “SYSTEM TROUBLE / SUP.” Indicator (Yellow) Flashing.
b) “ALARM OPEN” Indicator (Yellow) ON.
c) System trouble buzzer ON (Pulsing) - Press “SUP. / TRO. SIL.” button to silence.
d) Clear (repair) open to circuit to return to standby condition.
 )G9D38)E@5BF9C?BI0?>5
)8?BD9>CG9D38CE@5BF9C?BI39B3E9D)E@5BF9C?BI<1B=)ICD5=*B?E2<5
a) “SYSTEM TROUBLE / SUP.” Indicator (Yellow) steady.
b) “ZONE ALARM” Indicator (Yellow) ON.
c) System trouble buzzer ON (Steady) - Press “SUP. / TRO. SIL.” button to silence. System is now ready for subsequent
supervisory alarm i.e., next supervisory alarm condition will reinstate system supervisory alarm condition.
d) Press “SUP. / TRO. SIL.” button to silence.
e) Restore supervisory circuit or initiating device. Press “SYS. RST.” button to return to standby condition.
%@5>9>CG9D38CE@5BF9C?BI39B3E9D)E@5BF9C?BI*B?E2<5)ICD5=*B?E2<5
a) “SYSTEM TROUBLE / SUP.” Indicator (Yellow) Flashing.
b) “ZONE TROUBLE” Indicator (Yellow) ON.
c) System trouble buzzer ON (Pulsing) - Press “SUP. / TRO. SIL.” button to silence.
d) Repair open to return to standby condition.
~ 14 ~
Vedere la pagina 16
1 2 ... 12 13 14 15 16 17 18 19 20 21 22 ... 62 63

Commenti su questo manuale

Nessun commento